Rigid copper conductor with Insulation and Sheath of Cross- linked Silicone Rubber
We build fast, flexible silicone cable solutions — grounded in precision, driven by partnership, and proven in the field.
We build fast, flexible silicone cable solutions — grounded in precision, driven by partnership, and proven in the field.
1 – Single-core copper conductor class 1 or multi-core class 2, according to EN 60228
2 – Cross-linked silicone rubber insulation, halogen-free, fire and flame retardant, according to VDE 0266:2000
3 – The insulated conductors are concentrically twisted together
Reference standard
Nominal operating voltage Uo/U
Test voltage
Resistance to flame propagation
DIN VDE 0266 (VDE 0266): 2000-03
600/1000 V
according to EN 50395, 9.6 kVDC, for 5 minutes / each conductor
according to EN 60332-3-24, cat. C
Reference standard
DIN VDE 0266 (VDE 0266): 2000-03
Nominal operating voltage Uo/U
600/1000 V
Test voltage
according to EN 50395, 9.6 kVDC, for 5 minutes / each conductor
Resistance to flame propagation
according to EN 60332-3-24, cat. C
No corrosive gas emissions
according to VDE 0472 part 813
Smoke density
according to VDE 0472 part 816
Ambient temperature when
installing the cable
– 10 °C ÷ +50 °C
Ambient temperature
during cable operation
– 60 °C ÷ +180 °C
Maximum temperature of objects
it can come into contact with
+180 °C
No corrosive gas emissions
according to VDE 0472 part 813
Smoke density
Ambient temperature when
installing the cable
according to VDE 0472 part 816
– 10 °C ÷ +50 °C
Ambient temperature
during cable operation
– 60 °C ÷ +180 °C
Maximum temperature of objects
it can come into contact with
+180 °C